Although the VFD drive is a stationary device, the filter capacitors and the cooling fans are power-consuming components. Therefore, the main limiting factors for the lifespan of the VFD drive are the electrolytic capacitors and the fans. A good installation environment and reducing the ambient temperature can extend the lifespan of the VFD drive (typically, for every 10℃ increase in ambient temperature, the lifespan of the VFD drive will be halved).
How long is the lifespan of components?
Electrolytic Capacitor:
The standard lifespan is 5 years due to the natural evaporation of the electrolyte;
Cooling Fan:
The standard lifespan is 2-3 years due to the aging of the lubricating oil.
When will the service life be about to end?
Electrolytic Capacitor:
1. Compared with other machines, the LED lights go out too quickly after power failure;
2. Frequent low-voltage alarms occur;
Cooling Fan:
1. When the fan is running, there is a rubbing sound;
2. When the power is cut off, it stops quickly.
You may be interested in
- All
- Product Management
- Blog
- Introduction Content
- Corporate outlets
- Frequently Asked Questions
- Corporate Video
- Corporate Portfolio
Contact Us
Changsha Best Electric Technology Co., Ltd
Tel: +86 731-8871-9138
WhatsApp: +86 15974246245
E-mail: sales@best-cn.cn
Address: Changsha Best Electric Industrial Park, Dong Fang Hong Street, Yuelu District, Changsha, Hunan, China
导航下拉添加类名.active
屏蔽页面上图片的alt/title提示
图片alt标题设置: BEST
表单验证提示文本: Content cannot be empty!
循环体没有内容时: Sorry, no matches were found.
CSS / JS 文件放置地